Integrated Dry Cooling Unit for AI & Data Centers
Core Technical Advantages
-
All-in-One Containerized Design Combines high-efficiency finned-tube heat exchangers, EC fan arrays, pump modules, and control systems into a standard container form factor, eliminating complex on-site assembly.
-
High-Performance Heat Rejection Large-area finned tube design paired with variable-speed EC fans maximizes air-side heat transfer, effectively rejecting waste heat from closed liquid loops without reliance on chilled water systems.
-
Rugged Outdoor-Ready Build Built to ISO container standards, the unit features weather-resistant enclosures, corrosion-proof coatings, and vibration-dampening structures for long-term reliability in diverse environments.
-
Plug-and-Play Deployment Pre-tested piping, pumps, and controls enable rapid connection to CDU, cold plate, and manifold systems, cutting on-site commissioning time by over 50%.
-
Low-Noise & Energy-Saving Operation Variable-speed fans and pumps dynamically adjust flow based on coolant temperature, reducing power consumption and lowering data center PUE for sustainable, green computing.
Product Specifications
|
Attribute |
Specification |
|
Brand |
EXTRCOOL |
|
Model Series |
IDCU-Series Integrated Dry Cooling Unit |
|
Cooling Type |
Air-to-Liquid Dry Cooling |
|
Product Category |
Containerized Heat Rejection Unit |
|
Compatible Systems |
CDU, liquid cooling racks, cold plate loops |
|
Place of Origin |
Guangdong, China |
Ideal Application Scenarios
- AI Data Centers: Provides reliable heat rejection for GB200/GB300 GPU liquid cooling systems, supporting high-density AI training workloads.
- HPC & Supercomputing Clusters: Delivers turnkey cooling for scientific computing and engineering simulation liquid cooling loops.
- Retrofit Air-to-Liquid Cooling: Enables low-cost upgrades for traditional air-cooled data centers without chilled water infrastructure.
- Edge & Colocation Data Centers: Supports outdoor, space-constrained deployments with compact, containerized form factors.
- Hybrid Liquid Cooling Architectures: Seamlessly integrates with CDU systems to enable partial or full liquid cooling solutions.
Why Choose EXTRCOOL Integrated Dry Cooling Unit?
The integrated design eliminates the need for separate dry cooler, pump, and control room construction, offering a low-cost, scalable heat rejection solution for liquid cooling data centers. EXTRCOOL’s all-in-one unit combines high thermal efficiency, rugged durability, and simplified deployment to meet the evolving needs of AI and HPC workloads, ensuring stable, low-noise, and energy-efficient operation year-round.
Frequently Asked Questions
1.What is an Integrated Dry Cooling Unit used for?
It is a containerized, all-in-one heat rejection solution for liquid cooling systems, combining dry cooler, pumps, and controls into a single package. It eliminates the need for complex chilled water infrastructure, making it ideal for data centers seeking rapid deployment and low maintenance.
2.What are the benefits of an integrated vs. standalone dry cooler?
The integrated unit offers faster deployment, simplified commissioning, and reduced on-site engineering work. It is fully pre-tested at the factory, minimizing the risk of installation errors and ensuring consistent performance from day one.
3.Is the unit compatible with all CDU systems?
EXTRCOOL’s integrated dry cooling units support standard liquid loop pressures and temperatures, with customizable flange connections to match most commercial CDU systems. Contact our engineering team for tailored compatibility verification.
Product Specification
| Product Type | Dry cooler(DC) | ||||||
| Part Number | EXT-150DC | EXT-200DC | EXT-300DC | EXT-600DC | EXT-1000DC | EXT-1600DC | EXT-2000DC |
| Installation Type | Horizontal installation | ||||||
| Rated cooling capacity | 150kW | 200kW | 300kW | 600kW | 1000kW | 1600kW | 2000kW |
| Coolant | PG40 | PG40 | PG40 | PG40 | PG40 | PG40 | PG40 |
| Working environment T&H | -30℃~45℃/RH5 ~90% | ||||||
| Storage environment T&H | -45℃~ 70℃/RH5~93% | ||||||
| Air& Liquid temp gap | 10℃/5℃ | 10℃/5℃ | 10℃/5℃ | 10℃/5℃ | 10℃/5℃ | 10℃/6.5℃ | 10℃/6.5℃ |
| Air temp.(in/ out) | 30℃/40℃ | 30℃/40℃ | 30℃/40℃ | 30℃/40℃ | 30°C/40°C | 30°C/40℃ | 30℃/40℃ |
| Secondary side liquid temp.(out/ in) | 35℃/40℃ | 35°C/40°C | 35°C/40°C | 35℃/40℃ | 38°C/43℃ | 35℃/41.5℃ | 38℃/44.5℃ |
| Air flow rate | 50000m³/h | 60000m³/h | 100000m³/h | 240000m³/h | 300000m³/h | 540000m³/h | 600000m³/h |
| Liquid flow rate | 500LPM | 650LPM | 1000LPM | 2000LPM | 3200LPM | 4000LPM | 5000LPM |
| Power Supply | 3P AC380V 50/60Hz 3PAC480V 60Hz |
||||||
| Dual power ATS | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
| Controltype | PID control method, regulating fan speed based on temperature sensor(supply/ return water) | ||||||
| Leak Detection | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
| Redundant Fan Automatic Switchover | N+1 | N+1 | N+1 | N+1 | N+1 | N+1 | N+1 |
| Power consumption | < 5kW | <8kW | <12kW | <28kW | <32kW | <58kW | <67kW |
| Communication | Modbus RTU&TCP/IP | ||||||
| Design pressure | >10Bar | >10Bar | >10Bar | > 10Bar | >10Bar | >10Bar | > 10Bar |
| Approx. Weight | 800kg | 1200kg | 1650kg | 3800kg | 4000kg | 7800kg | 8000kg |
| Protection level | IP55 | IP55 | IP55 | IP55 | IP55 | IP55 | IP55 |
| Dimensions(W x D x H) mm | 1850*2200*2100 | 2250*2200*2100 | 2850*2200*2100 | 5800*2280*2535 | 5800*2280*2535 | 11900*2280*2535 | 11900*2280*2535 |